SZ11 10kV oil-immersed on-load voltage regulating transformer

SZ11 10kV oil-immersed on-load voltage regulating transformer

产品概述:The oil-immersed distribution transformer produced by our company adopts a new insulation structure to improve the short-circuit resistance; the iron core is ma···

产品简介

Features

Structural features

The oil-immersed distribution transformer produced by our company adopts a new insulation structure to improve the short-circuit resistance; the iron core is made of high-quality cold-rolled silicon steel sheet; the high-voltage windings are made of high-quality oxygen-free copper wire, and Adopt multi-layer cylindrical structure; all solid parts are treated with special anti-loosening treatment.

Technical Features

The product has the characteristics of high efficiency and low loss, which can save a lot of power consumption and operating costs, and has significant social benefits. It is a popular new technology product.

reliable structure

structural improvement

1. Spiral coil with longitudinal oil channel, better internal heat dissipation;

2. The effective support of the coil end face is improved, and the ability to resist short-circuit current is stronger;

3. A new hoisting structure and body positioning structure are adopted to ensure more reliability in long-distance transportation and operation;

4. We also have many unique and reliable structures to serve you;

5. Selecting a transformer with a higher performance level will have a higher level of technical content.

high quality material

Oxygen-free copper wire

Oxygen-free copper wire with lower resistivity is selected, and after a series of additional surface treatments, it is smoother and has no burr sharp corners, so that the load loss of the transformer is lower and the electrical performance is more reliable.

High quality silicon steel sheet

High-quality silicon steel sheets are selected, and with the improvement of performance level, silicon steel sheets with lower unit loss are used, so that the no-load loss of the transformer is lower.

Premium quality laminated wood insulation

Choose high-quality laminated wood insulation, never crack, even under the action of short-circuit current, it will not move.

Deep filtered transformer oil

Using deep-filtered transformer oil with lower water, gas and impurity levels, the transformer works more reliably.

High quality rubber sealing material

Use high-quality rubber sealing materials to effectively prevent aging and prevent leakage.

Raw materials are inspected

There are quality inspections of raw materials, and all raw material manufacturers have undergone strict inspections in accordance with the national standard ISO9000.

Good technical and economic performance

Performance

On the basis of the S9 series, the S11 series products have an average no-load loss reduction of 30%; no-load current is reduced by 70-85% compared with S9; It can still operate for a long time under the conditions of high temperature; the operating noise of the product is reduced by 2-4 decibels on average.

fully sealed

Improved sealing structure

The oil tank adopts a fully-sealed structure. Compared with the ordinary oil-immersed transformer, the fully-sealed distribution transformer cancels the oil conservator. The wave fin of the oil tank replaces the oil pipe as the cooling and heat dissipation element. The corrugated oil tank is made of high-quality cold-rolled sheet on a special production line. , The wave fin can expand and shrink the volume of transformer oil, so as to isolate the transformer from the atmosphere, prevent and slow down the oil deterioration and insulation moisture, enhance the operational reliability, and maintain normal operation without maintenance. The surface of the corrugated fuel tank is coated with conformal paint after degreasing, rust removal and phosphating treatment, which is suitable for use in metallurgy, petrochemical, mining and other environments.

Transformer Product Standard

GB

GB 1094.1-1996 GB 1094.2-1996 JB/T10088-2004 GB 1094.3-2003 GB 1094.5-2003 GB/T 10237-1988 GB/T 6451-2008 GB/T 7595-1987 JB/T 3837-2010

Transformer usage conditions

Altitude

not more than 1000m

ambient temperature

The highest temperature +40℃ The hottest month average temperature+30℃ The highest annual average temperature+20℃The outdoor minimum temperature is -25℃


Transformer special conditions of use (detailed when ordering)

Altitude

over 1000m

ambient temperature

Maximum temperature +40℃ Minimum temperature -25℃


10KV class SZ11 series on-load voltage regulating oil-immersed power transformer technical parameters (2000kVA~12500kVA double-winding on-load voltage regulating transformer)

Rated capacity (kvar) 

Voltage combination and tap range (kv) 

link group label

No-load loss (W)

Load loss (W)

No-load current (%)

Short circuit impedance )

Weight (kg)

Dimensions (mm) length Lx width Bx height H)

Installation size

High voltage (kV) 

High pressure tap range %

Low voltage (kV) 

Body lifting weight

oil weight

gross weight

200

6.3 10 10.5 11







±4x2.5 %

6.3 6.6 10.5 11





Yyno Dyn11

380

2900

1

4.0

480

230

860

1360x820x1130

550/550

250

440

3420

0.9

570

250

980

1420x840x1150

550/550

315

530

4100

0.9

650

260

1100

1520x1000x1230

550/550

400

640

4950

0.8

740

300

1280

1520x950x1260

660/660

500

760

5890

0.8

880

340

1490

1600x1030x1300

660/660

630

960

7260

0.6

5

1020

370

1740

1740x1180x1320

660/660

800

1120

8890

0.6

1210

450

2100

1800x1220x1420

660/660

1000

1360

10400

0.6

1400

520

2480

1850x1240x1520

820/820

1250

1560

12300

0.5

1640

620

2950

1860x1280x1610

820/820

1600

1920

14700

0.5

1890

620

3250

1900x1300x1650

820/820

2000

2270

18600

0.4

5

2180

730

3870

2230x1850x2050

820/820

2500

2680

21600

0.4

2670

820

4470

2360x1880x2100

820/820