S11 series 20kV oil-immersed power transformer

S11 series 20kV oil-immersed power transformer

产品概述:The oil-immersed distribution transformer produced by our company adopts a new insulation structure to improve the short-circuit resistance; the iron core is ma···

产品简介

Features

Structural features

The oil-immersed distribution transformer produced by our company adopts a new insulation structure to improve the short-circuit resistance; the iron core is made of high-quality cold-rolled silicon steel sheet; the high-voltage windings are made of high-quality oxygen-free copper wire, and Adopt multi-layer cylindrical structure; all solid parts are treated with special anti-loosening treatment.

Technical Features

The product has the characteristics of high efficiency and low loss, which can save a lot of power consumption and operating costs, and has significant social benefits. It is a popular new technology product.

reliable structure

structural improvement

1. Spiral coil with longitudinal oil channel, better internal heat dissipation;

2. The effective support of the coil end face is improved, and the ability to resist short-circuit current is stronger;

3. A new hoisting structure and body positioning structure are adopted to ensure more reliability in long-distance transportation and operation;

4. We also have many unique and reliable structures to serve you;

5. Selecting a transformer with a higher performance level will have a higher level of technical content.

high quality material

Oxygen-free copper wire

Oxygen-free copper wire with lower resistivity is selected, and after a series of additional surface treatments, it is smoother and has no burr sharp corners, so that the load loss of the transformer is lower and the electrical performance is more reliable.

High quality silicon steel sheet

High-quality silicon steel sheets are selected, and with the improvement of performance level, silicon steel sheets with lower unit loss are used, so that the no-load loss of the transformer is lower.

Premium quality laminated wood insulation

Choose high-quality laminated wood insulation, never crack, even under the action of short-circuit current, it will not move.

Deep filtered transformer oil

Using deep-filtered transformer oil with lower water, gas and impurity levels, the transformer works more reliably.

High quality rubber sealing material

Use high-quality rubber sealing materials to effectively prevent aging and prevent leakage.

Raw materials are inspected

All raw material manufacturers have passed the strict inspection according to the national standard ISO9000.

Good technical and economic performance

Performance

On the basis of S9, S11 series products have an average reduction of 30% in no-load loss; no-load current is reduced by 70-85% compared with S9; It can still run for a long time under the conditions; the operating noise of the product is reduced by 2-4 decibels on average.

fully sealed

Improved sealing structure

The oil tank adopts a fully-sealed structure. Compared with the ordinary oil-immersed transformer, the fully-sealed distribution transformer cancels the oil conservator. The wave fin of the oil tank replaces the oil pipe as the cooling and heat dissipation element. The corrugated oil tank is made of high-quality cold-rolled sheet on a special production line. , The wave fin can expand and shrink the volume of transformer oil, so as to isolate the transformer from the atmosphere, prevent and slow down the oil deterioration and insulation moisture, enhance the operational reliability, and maintain normal operation without maintenance. The surface of the corrugated fuel tank is coated with conformal paint after degreasing, rust removal and phosphating treatment, which is suitable for use in metallurgy, petrochemical, mining and other environments.

Transformer Product Standard

GB

GB 1094.1-1996 GB 1094.2-1996 JB/T10088-2004 GB 1094.3-2003 GB 1094.5-2003 GB/T 10237-1988 GB/T 6451-2008 GB/T 7595-1987 JB/T 3837-2010

Transformer usage conditions

Altitude

not more than 1000m

ambient temperature

The highest temperature +40℃ The hottest month average temperature +30℃ The highest annual average temperature +20℃ The outdoor minimum temperature is -25℃


Transformer special conditions of use (detailed when ordering)

Altitude

over 1000m

ambient temperature

Maximum temperature +40℃ Minimum temperature -25℃


20kV S11 series oil-immersed distribution transformer technical parameters

Rated capacity (kvar)

Voltage combination and tap range (kv)

link group label

No-load loss (W)

Load loss (W)

No-load current %)

Short circuit impedance (%)

Body lifting weight

oil weight

gross weight

Dimensions (mm) (length Lx width Bx height H)

Installation size

High voltage (kV)

High pressure tap range %

Low voltage (kV)

50

20 22 24



±5% ±2x2.5%

0.4

Yyno Dyn11 Yzn11



130

1010/960

1.3

5.5

210

100

380

780x540x960

400/400

63

150

1200/1150

1.2

240

115

430

810x560x970

400/400

80

180

1440/1370

1.2

280

125

490

840x580x990

400/400

100

200

1730/1650

1.1

310

130

540

950x580x1050

400/400

125

240

2080/1980

1.1

360

140

590

960x580x1060

400/400

160

280

2540/2420

1

430

160

700

1040x650x1090

550/550

200

340

3000/2860

1

490

190

820

1140x720x1120

550/550

250

400

3520/3350

9

560

200

920

1220x800x1150

550/550

315

480

4210/4010

9

630

230

1050

1250x820x1180

550/550

400

570

4970/4730

0.8

740

250

1220

1350x900x1210

660/660

500

680

5940/5660

0.8

910

280

1450

1450x980x1260

660/660

630

810

6820

6

6

1050

340

1710

1600x1070x1290

660/660

800

980

8250

0.6

1200

390

1970

1660x1160x1350

660/660

1000

1150

11330

0.6

1440

440

2350

1800x1260x1420

820/820

1250

1360

13200

0.5

1640

510

2700

1820x1300x1450

820/820

1600

1640

15950

0.5

1960

580

3330

1870x1320x1550

820/820

2000

1940

19140

0.4

2290

750

4160

1900x1350x1650

820/820

2500

2290

22200

0.4

2800

780

4600

2050x2000x2100

820/820

Note: 1. According to the requirements of the user department, the transformer with low voltage of 0.69kV can be provided. 2. Above the slash is the loss of Dyn11 or Yzn11.


20kV/10kV S11 series oil-immersed distribution transformer technical parameters

Rated capacity (kVA)

Voltage combination (kV)

Connection method

Impedance voltage (%)

Loss (kW)

No-load current (%)

Weight (kg)

Dimensions (mm) (length Lx width Bx height H)

Gauge Longitudinal / Transverse

high pressure

low pressure

no load

load

weight

oil weight

gross weight

50

20/10

0.4

Dyn11 Yyno

5.5

0.17

1.15

2

200

185

515

920x610x1150

450/380

100

0.23

1.92

1.8

330

210

695

920x680x1250

550/450

125

0.27

2.26

1.7

395

235

810

960x780x1270

550/470

160

0.29

2.69

1.6

505

255

950

1160x710x1330

550/520

200

0.34

3.16

1.5

580

280

1065

1190x730x1340

550/520

250

0.41

3.76

1.4

695

300

1200

1280x820x1360

650/550

315

0.49

4.53

1.4

745

320

1360

1380x910x1390

650/550

400

0.58

5.47

1.3

865

370

1580

1430x950x1470

650/550

500

0.69

6.58

1.2

985

400

1790

1520x1020x1510

750/600

630

0.83

7.87

1.1

1165

460

2100

1680x1150x1530

850/660

800

0.98

9.41

1

1335

495

2420

1810x1280x1580

850/660

1000

1.15

11.54

1

1655

590

3080

1840x1290x1690

850/660

1250

1.4

13.94

0.9

1890

630

3460

1850x1300x1730

850/660

1600

1.7

16.67

0.8

2220

710

4015

1920x1350x1790

850/700

2000

2.18

20.43

0.8

2530

830

4555

2020x1770x2290

820/820

2500

2.56

21.85

0.8

3165

905

5400

2080x1800x2280

1070/1070

Note: High voltage tap range ±5% or ±2x2.5%; frequency 50Hz;


1.jpg


Excel Energy Co., Ltd.

0577-62789660

(联系电话 7×24)