产品概述:Supports 1+1 cross-cabinet parallel operation + Power E is a modular UPS system consisting of 1 to 3 modules. Users can easily expand the capacity of the UPS th···
Support 1+1 cross-cabinet parallel operation
+Power E is a modular UPS system consisting of 1 to 3 modules. Users can easily expand the capacity of the UPS through plug-and-play power modules. In addition, this UPS system has battery packs stacked on the rack for a smaller footprint. It is the perfect power solution for small and medium businesses.
main feature
●N+1 or N+R1 parallel redundant application design increases system flexibility, stability and security
●High-efficiency double-conversion online UPS system
●Output power factor 1.0
●Modular design, easy to expand, update and maintain, which can reduce after-sale maintenance costs
●The number of battery cells is adjustable
●The charging current is adjustable
●Built-in maintenance bypass switch
5.7” LCD graphic design, the display is more direct and clear
Product Specifications
| MODEL | +Power E 15U-60 | +Power E 15U-90 | |
| phase | 3-phase in/3-phase out | ||
| Battery Type | External Battery | ||
| Maximum cabinet capacity | 60KW | 90KW | |
| maximum power module | 3 | ||
| Power Module Capacity | 20KVA/20KW | 30 KVA / 30 KW or 20 KVA / 20KW | |
| ENTER | |||
| voltage range | 305 ~ 478 VAC at 70% - 100% load; 208 ~ 478 VAC for <70% load | 305~478 VAC at 70%-100% load; 208~478 VAC for <70% load | |
| Rated voltage | 3 x 380VAC/400VAC/415VAC (3Ph+N) | ||
| Frequency Range | 40Hz ~70Hz | ||
| Rated frequency | 50/60 Hz (Auto sensing) | ||
| power factor | > 0.99 at 100% load, >0.98 at 50% load | ||
| Harmonic Distortion (THDi) | < 3% @ 100% load | ||
| OUTPUT | |||
| Rated frequency | 50/60Hz | ||
| overload capacity | 1 hour for 110%, 10 mins for 125%, 1 min for 150% and 200ms for >150% | ||
| Voltage regulation (steady state) | ≦ ±1% Typical (balanced load); ≦ ±2% Typical (unbalanced load) | ||
| Rated voltage | 3 x 380VAC/400VAC/415VAC (3Ph+N) | ||
| efficiency | Up to 94.5% | ||
| Harmonic Distortion | ≦ 2% THD (Linear Load); ≦ 4% THD (Non-linear Load) | ||
| Frequency range (sync range) | 46Hz~54Hz or 56Hz~64Hz | ||
| BATTERIES AND CHARGERS | |||
| float voltage | 2.25V/Cell | ||
| boost charging voltage | 2.35V/Cell | ||
| Maximum charging current | 8A for 30KW power module (User-djustable); 6A for 20KW power module (User-adjustable) | ||
| maximum voltage | +/- 240V (12V x 40 Pcs) | ||
| Rated voltage | +/- 216V (12V x 36 Pcs) | ||
| Temperature compensation | Yes | ||
| Minimum voltage | +/- 192V (12V x 32 Pcs) | ||
| SURROUNDINGS | |||
| Altitude | <1000m for Nominal power | ||
| IP class | IP 20 | ||
| Operating temperature | 0~40℃ | ||
| Working humidity | 0~95% non-condensing | ||
| PHYSICS | |||
| Cabinet Dimensions, D X W X H (mm) | 1000 x 515 x 763 | ||
| Net weight (kg) | 182 | 183.5 | |
| MANAGE | |||
| Optional SNMP | Power management from SNMP manager and web browser | ||
| Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC | ||
| STANDARD | |||
| Safety verification | IEC/EN 60950-1; IEC/EN 62040-1 | ||