Special Reactor

Special Reactor

产品概述:Special reactors are used in specific environments, and are connected in series or in parallel with the power grid to absorb harmonic currents of corresponding ···

产品简介

Special reactors are used in specific environments, and are connected in series or in parallel with the power grid to absorb harmonic currents of corresponding frequencies in the power grid. Make the electrical equipment in the system operate normally and safely.


Structural features

phase

The reactor is divided into three-phase and single-phase two, both are iron core dry type

iron core

The iron core is made of high-quality and low-loss special materials. The core column is divided into uniform small sections by multiple air gaps. The air gaps are separated by epoxy laminated glass cloth boards and bonded with special adhesives to ensure that the reactance air gaps are in the process of operation. no change

coil

The coils are wound with class H or class C enamelled flat copper wire or copper foil, arranged closely and evenly

Reactor

The coil and iron core of the reactor are assembled into one body and then go through the process of pre-baking→vacuum dipping→heat-baking and curing, and the H-level dipping varnish is used to firmly combine the coil and the iron core of the reactor.

clip

The clips and fasteners of the reactor are made of non-magnetic materials to ensure that the reactor has a high quality factor and a good filtering effect.

Exposed parts

The exposed parts are treated with anti-corrosion treatment, and the lead-out terminals are made of tinned copper tube terminals

Parameters and Standards

Performance parameters

1. Can be used in 400V, 660V, 1140V systems.

2. The rated insulation level is 5kV/min.

3. The temperature rise limit of each part of the reactor: the iron core does not exceed 45K, and the coil temperature rise does not exceed 55K.

4. The noise of the reactor is not more than 45dB.

5. The difference between any two-phase reactance values of the three-phase reactor is not more than ±3%.

6. Temperature resistance class H (180℃) or above.

Use environmental conditions

1. The altitude does not exceed 2000 meters.

2. The operating ambient temperature is -25℃~+45℃, and the relative humidity does not exceed 90%.

3. There is no harmful gas around, no flammable and explosive materials.

4. The surrounding environment should have good ventilation conditions. If it is installed in the cabinet, ventilation equipment should be installed.

other

download Google

1. Product model

2. Rated current

3. Rated voltage (grid voltage)

4. Rated inductance

5. Insulation class

6. Other special requirements can be specified in the agreement


Excel Energy Co., Ltd.

0577-62789660

(联系电话 7×24)